• Five boiler outputs ranging from 125kW to 300kW as a single boiler and 430kW, 520kW and 600kW using a duo cascade kit to meet the heat requirements in all sizes of building
  • Efficiency up to 106.6% net (up to 95% gross) making maximum use of the energy it uses
  • Lightweight aluminium heat exchanger for reliable, highly efficient heat transfer
  • 6:1 modulation ratio to meet variable heating requirements, ensuring optimum energy efficiency and running costs
  • Top mounted hydraulic and flue connections which are easier to connect and require less space for working access
  • Compact dimensions and small footprint means less space is needed for installation

 

Specification

Model     125 170 215 260 300
Performance Fuel type

Output @ 80 / 60oC

NG

kW

121.6

165.8

210.1

254.5

294

Output @ 50 / 30oC

NG

kW

133.1

181.3

229.6

278.1

322.1

Input (Gross) Maximum

NG

kW

138.7

188.7

238.6

288.6

333

Output @ 80 / 60oC

LPG

kW

121.6

165.9

210.2

254.8

294.4

Output @ 50 / 30oC

LPG

kW

133.1

181.5

229.8

278.5

321.7

Input (Gross) Maximum

LPG

kW

138.7

188.7

238.6

288.6

333

Efficiency

Efficiency @ 80 / 60oC - 100% Load

 

% Gross  

87.7

87.8

88.0

88.2

88.3

Efficiency @ 50 / 30oC - 30% Load

 

% Gross

97.4

97.5

97.4

97.5

97.4

Current Building Regs - Part L2 Seasonal Efficiency

 

% Gross

96.5

96.6

96.7

96.8

97

Gas 

Gas Consumption (Natural Gas)

 

m3/h

13.2

18

22.8

27.5

31.7

Gas Consumption (LPG)

 

kg/h

9.7

13.2

16.7

20.2

23.3

Inlet Gas Pressure (Natural Gas G20)

 

m/bar

18 - 25

Inlet Gas Pressure (LPG G33)

 

m/bar 

37

Gas Connection Size

 

inch

1"

1.5"

1.5"

1.5"

1.5"

Gas Connection Type

 

 

Male Thread

Flue

Flue Gas Volume @ 80/60oC

NG

m3/h@STP

172.2

234.2

296.2

358.3

413.4

Flue Gas Volume @ 50/30oC

NG

m3/h@STP

157.3

214

271

327.8

378.3

Flue Gas Volume @ 80/60oC

LPG

m3/h@STP

149.1

202.9

256.5

310.3

358

Flue Gas Volume @ 50/30oC

LPG

m3/h@STP

136.2

185.4

234.7

283.9

327.6

Max Flue Gas Pressure @ Outlet

 

m/bar 

1

1

1

1

1

Hydraulic

Water Flow Rate @ 11oC ΔT

 

l/s

2.65

3.61

4.57

5.54

6.4

Water Flow Rate @ 20oC ΔT

 

l/s

1.46

1.98

2.51

3.05

3.52

Hydraulic Resistance @ 11oC ΔT

 

kPa

9

11

12.1

12.7

12.9

Hydraulic Resistance @ 20ºC ΔT

 

kPa

2.8

3.4

3.7

3.9

4

Water Content

 

Litres

29

34

38

45

53

Flow and Return Connection Size

 

mm

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

DN65 PN6

Flow and Return Connection Type

 

 

Flange

Flue Connection Size

 

mm

160

160

200

200

200

Max Boiler Operating Pressure

 

bar 

6

6

6

6

6

Min Boiler Operating Pressure

 

bar

1

1

1

1

1

Mac Flow Temperature

 

oC

85

85

85

85

85

General

 

 

 

 

 

 

 

Appliance Dry Weight

 

Kg

205

240

285

314

344

Dimensions W x D x H

 

mm

692 x 1008 x 1389

692 x 1008 x 1389

692 x 1171 x 1389

692 x 1264 x 1389

692 x 1357 x 1389

NOx Level (Dry @ 0% O2)

 

mg/kWh

38

38

39

39

39

CO2 Content

NG 

%

9.3

CO2 Content

LPG

%

11

Noise levels @ 1m from unit (sealed room)

 

dB(A)

66

67

67

67

68

High Level Ventilation* (BS6644)

 

cm2

250

340

430

520

600

Low Level Ventilation* (BS6644)

 

cm2

500

680

860

1040

1200

Electrical

 

 

 

 

 

 

 

Power Consumption

 

W

170

200

330

350

410

Nominal Supply Voltage

 

V/Hz

230 v 1 Ph 50 Hz

 

 

 

 

 

 

 

floor standing boilerDimensions and clearance measurements for all models of the Eurocondense four are featured in the tables below.

If you can't find the information you are looking for, you may find it within the product literature.

If you would like to speak to your local Area Sales Manager, please complete the online form within the enquiry tab.

 

Dimensions

 

Eurocondense four 125 170  215  260 300 
A Width 692 692 692 692 692
B Height 1389 1389 1389 1389 1389
C Depth 1008 1008 1171 1264 1357

 

Clearances

Eurocondense four 125 170 215 260 300
1 Front 1000 1000 1000 1000 1000
2 L Hand 500 500 500 500 500
3 Top 300 300 300 300 300
4 Back 500 500 500 500 500
5 R Hand 500 500 500 500 500

Learn more about the Eurocondense four by downloading our product literature.

Download your Building Information Modeling (BIM) object(s) for this product.

Download CAD files for this product using the links below. To access CAD files you will need the correct software installed to allow you to open .dwg files such as AutoCAD

Interested in this product for your premises? Complete the form below and someone from the team will contact you shortly.

Alternatively, speak to your Area Sales Managers about this or any of our products. You can find their details here.

More Potterton Commercial boilers

Potterton Commercial logo and strapline
Connect with us on LinkedinFollow us on TwitterWatch our videos on YouTube